Short circuit ratio (SCR)

Updated 2026-10-27

Data records

  • In IEEE 519-2022 the short circuit ratio at a location is the available short circuit current divided by the maximum demand load current, both in amperes, which makes the ratio dimensionless. Source: IEEE 519-2022, clause 3.1. Verified 2026-10-27. Record qty.short-circuit-ratio.ieee519.definition
  • In IEEE 519-2022 the short circuit ratio at the point of common coupling selects the row of Table 2, Table 3 or Table 4 that applies to a user, with the most restrictive row for the weakest supply and a footnote holding power generation facilities to that row regardless of their ratio. Source: IEEE 519-2022, clause 5.3. Verified 2026-10-27. Record qty.short-circuit-ratio.ieee519.use
  • The term is written Short circuit ratio (SCR). Value: Short circuit ratio (SCR). Source: Electrical Testing Reference editorial taxonomy, 2026-10 edition. Verified 2026-10-27. Record qty.short-circuit-ratio.title

Sources

  • Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
  • IEEE 519-2022, Harmonic Control in Electric Power Systems, 2022 edition, IEEE. Cited: clause 3.1; clause 5.3. Held as: Purchased single-user copy. Publisher page for IEEE 519-2022Publisher information page

Obtaining the documents

Changelog (3 entries)
DateRevisionChange
2026-10-27created (qty.short-circuit-ratio.ieee519.definition)
2026-10-27created (qty.short-circuit-ratio.ieee519.use)
2026-10-27created (qty.short-circuit-ratio.title)

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Short circuit ratio (SCR)." Power Quality Reference. 2026-10-27. https://www.powerqualityreference.com/quantities/short-circuit-ratio/.