Data record std.ieee-1159.structure.monitoring-location

Verified 2026-10-27 Confidence: High

Clause 7.3 of IEEE 1159-2019 places a monitor as close as possible to a symptomatic load, at the secondary of the service transformer for a facility-wide survey, and at the point of common coupling for an IEEE 519 comparison, and Table 3 maps the scope of a problem, one piece of equipment, one branch or the whole facility, to the recommended monitoring location.

ProvenanceIEEE 1159-2019 supports data record std.ieee-1159.structure.monitoring-location, which is cited on the entry IEEE Recommended Practice for Monitoring Electric Power Quality.SOURCEIEEE 1159-2019IEEE 1159-2019Licensed standard, clause 7.3DATA RECORDstd.ieee-1159.structure.monitoring-locationstd.ieee-1159.structure...Verified 2026-10-27ENTRYIEEE Recommended Practice for Monitoring Electric Power QualityIEEE Recommended Practic..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 1159-2019Licensed standard, clause 7.3
Data recordstd.ieee-1159.structure.monitoring-locationVerified 2026-10-27
EntryIEEE Recommended Practice for Monitoring Electric Power QualityNo revisions
Subject
IEEE Recommended Practice for Monitoring Electric Power Quality (Standards)
Kind
Standard scope
Source
IEEE 1159-2019, clause 7.3, Recommended Practice for Monitoring Electric Power Quality, IEEE. Publisher pagePublisher information page